|
The data calculated
above is the measurement error for a single instrument. The compounding
effect of multiple instrument error rates allows much greater uncertainty
in the outside air control application.
Effect of
Variable Respiration Rates
The final variable
that we will examine is N, the respiration rate, CO2
generation and their effects on ventilation. Is it realistic to
assume that everyone in a building will be seated, is of the same
size, sex, health, and consuming the same diet? Can all the other
factors that influence respiration rates be held constant?
When we examine
the range of activities and their impact on respiration, we find
that N can easily vary to 0.50 for walking, 0.60 for
Light machine work and 0.90 for the upper threshold of light
activity. All of these are cited in the Appendix to ASHRAE
Standard 62-1999. These figures assume a target ventilation rate
of 15 CFM. When the target is 20 CFM, then the range of N
varies from 0.40 for office work, to 0.50 for Walking. When these
are used to calculate the amount of ventilation per person, we come
up with the following range of rates.
|
Respiration
Rate
|
Actual
Outside Air
|
Activity
|
|
N
|
L/sec
|
CFM
/ person
|
|
|
0.30
|
7.3
|
14.5
|
Seated
|
|
0.40
|
9.7
|
19.4
|
Office
Work
|
|
0.50
|
12.1
|
24.2
|
Walking
|
|
0.60
|
14.5
|
29.0
|
Light
Machine Work
|
|
0.90
|
21.8
|
43.5
|
Upper
threshold of light activity
|
The point is
that any change from the minimum respiration and intake ventilation
target has dramatic impacts on the amount of ventilation required,
if 700 ppm above a constant outside CO2 rate is used.
Building
Codes
With regard
to the ventilation code issues, specifically the International Building
Code, we find no mention of CO2 in Chapter 4 of the International
Mechanical Code 2000 (sections 401 402 403)
on Ventilation. Nor could we find any mention of CO2 in Section
1002 of the 2000 Building Performance Code version of the IBC. All
references to ventilation are related to dilution rates
using acceptable outside air.
Our search could
find no code authorities that use CO2 concentration or mass balance
control as a substitute for ventilation rate requirements. The most
significant misinterpretation is the California Energy Commission
Title 24. The California Energy Code allows CO2 as an input to
estimate occupancy level in variable occupancy spaces only
and thereby the ability to reset the ventilation rate accordingly.
It does not indicate nor endorse CO2 for use as a direct input for
control of intake rates.
Conclusions
The preceding
citations, calculations, analysis and comments have attempted to
provide authoritative sources and their reasons for dissuading people
from using CO2 demand-controlled ventilation. The positions
represented have been supported by many that recognize the difficulties
of providing rate control, without a rate
input.
When stated
very simply: ASHRAE 62-1999 is the ventilation standard
for Indoor Air Quality in the United States. Both the Ventilation
Rate Procedure and the Indoor Air Quality Procedure
<Prev
1
2
3
4
5
6
7
8 Next>
|