|
quantify
the outside air requirements at each occupied space. This leads
us to conclude that the best way to insure compliance is to measure
and directly control intake air rates. In fact, it can be argued
that the outside air requirement at each occupied space, especially
in VAV systems, can only be accomplished reliably by the
direct and dynamic control of airflow rates
into the building and supply air into each occupied zone.
From the potential
errors in measurement to the interrelationship of the variables,
simple mathematical analysis has provided us with a clearer understanding
of some of the real problems in using CO2 inputs for direct control
of ventilation rates.
From this analysis
we can conclude that CO2 should not be used as the sole and direct
determinant for dilution ventilation rates, in most commercial and
institutional structures.
Why not? Consider
these arguments.
First, because
there is no direct relationship between interior CO2 levels and
the rate of air that is delivered to a space. Under limited
circumstances CO2 levels can be used to reset control set points
to optimize intake rates, but CO2 levels cannot quantify nor
relate directly to volumetric airflow rates. Inferences that
there is a direct relationship must be heavily qualified to hold
any truth.
Next, none of
the potential impacts examined have considered the effect of sampling
errors. Logic alone tells us that it is not possible for a single
point to provide an accurate average for a space, without
the measured element being perfectly distributed throughout the
entire space.
Also, remember
the strict assumptions required by the ASHRAE Mass Balance Equation,
without which any calculated ventilation estimates would be useless.
Lastly, the
conditions described by these assumptions can only occur at at
a very specific single point-in-time; measured with the use
of a single, highly accurate instrument; and with calculations made
that usually assume no measurement error. The attempted use of the
tracer-gas or mass balance method to evaluate ventilation effectiveness,
but used for ventilation control cannot be valid for use in a dynamic
building system or operating environment.
Recommendations
Avoid all
indirect methods of measurement and control.
The best and
most secure method of outside air intake control is direct measurement.
With a direct, real-time electronic input any number of HVAC strategies
can be realized to optimize energy usage, through dynamic control
under changing internal and environmental conditions. Instrument
first-cost is not a valid justification to accept ineffective methodologies.
Many excuses have been levied for the avoidance of direct outside
air measurement, the most pervasive being cost and the difficulties
found in applying traditional technologies to field conditions.
But, these excuses are countered with several products and methods
that provide both cost-effective means and reliability in performance,
when used for outside air control.
Digital electronic
airflow measurement products are available for commercial HVAC applications
with acquisition costs comparable to traditional technologies, and
several methods of CO2 control.
Direct electronic
airflow measurement possesses a number of other advantages, including:
- sensor accuracy
better than ± 2% of Reading
- permanent
factory calibration to NIST-traceable air speed standards,
- no field
calibration requirements,
- zero maintenance
requirements,
- simple installation
for either new or existing HVAC equipment,
- linear analog
or digital electronic outputs, and maybe best of all --
- minimal duct
placement limitations,
Why risk the
energy and liability consequences of indirect measurements, when
direct control of outside air intake rates can be accomplished (in
most situations): economically, effectively and reliably?
<Prev
1
2
3
4
5
6
7
8
|