|

Figure #12:
Continuous Building Pressurization Control
ASHRAE
Standard 62-1999, Ventilation for Acceptable Indoor Air Quality
only peripherally address the need to maintain humidity control.
In Section 5.10 & 11 of Standard 62, habitable spaces are required
to have between 30% and 60% relative humidity. Section 5.12 &
13 require occupied spaces, ducts, and plenums not to exceed 70%
relative humidity. Nothing is said regarding air and moisture infiltration
related to mold generation.26 It is left to the designer's imagination
to protect the owner.
CONVENTIONAL
CONTROL STRATEGIES
HVAC control strategies are strongly influenced by the initial acquisition
cost of equipment. The pressure to cut costs on HVAC systems has
helped to amplify the IAQ problem in many buildings. Several methods
are used on the majority of designs as pressure control strategies,
either directly or indirectly. They often result in negative pressure
buildings and are detailed below.
Control
Scheme #1:
Fixed Outside Air Damper (Supply Fan Only Systems)
Active
pressurization control is often ignored on systems without return
or relief fans. However, if more air is mechanically exhausted from
the building than is brought in through the air handler, the building
will be negative to its environment. From direct observation and
anecdotal references, we know that many cases exist where external
pressures induced on the intake system result in outside air intakes
acting as an exhaust.
Systems
only having a supply fan appear to be almost exclusively set up
by Test and Balance contractors and have no active control for outside
air intake flow rates, and therefore no direct control of building
pressurization. In most cases, a fixed minimum outside air intake
damper is set to allow for the proper amount of outside air. Changes
in wind and stack effect will result in significant airflow variations
of the outside air intake on both constant volume (CV) and variable
air volume (VAV) systems.1, 2, 3, 29 VAV systems are far worse due
to the modulation of supply airflow rates and the resulting changes
in mixed air plenum pressure, which directly impacts the amount
of outside air allowed to enter the system.1, 2, 3, 29 Building
pressure is also affected, if the system does not include a method
of reliable pressure relief or exhaust.
Control
Scheme #2:
VFD Proportional Drive Slaving (Systems with a Return or Relief
Fan)
VFD
proportional drive slaving is very common. In fact, many manufacturers
of VFD units allow for the programming of a fan performance curve
into a VFD controller. Unfortunately, unless the duct system being
controlled has a constant system resistance, this technique is not
valid for fan tracking. The errors generated are
<Prev
1
2
3
4
5
6
7
8 9
10
11
Next>
|