Home | Products | Support | Literature | Contact Us | News | Representative Locator | Catalog Registration | IAQ Resources | Giveaway Registration | Site Map

amplified during an economizer cycle on supply/return fan systems since the damper’s non linear control characteristics complicates the pressure effects on both the supply and return fans 27, 28 .

Ideally, both the supply fan and return fan follow each other when the drive signals are changed. For example, if during system setup the supply fan speed is reduced from 100% to 50%, it is generally assumed that the same (or proportional) reduction to the return fan VFD (or increase to the relief fan VFD) will result. Unfortunately, the supply fan is reacting to both changes to RPM and changes to system resistance due to the variable positions of VAV boxes. Remember that the return fan is essentially reacting to a fixed resistance system. As a result, the supply fan operates within an "area" of the fan curve, rather than along a single curve as the return fan does. The resulting errors during operation are significant, although conditions appear to track properly during setup 27 (Figure #3).


Figure #3 - VFD Proportional Drive Slaving (operational example)

Typical fan curve illustrates the changes in airflow rates at a given RPM on VAV systems. The supply fan responds within an area of the fan curve (shaded oval) rather than simply a line or curve. As a result, systems that use VFD proportional drive slaving techniques can have dramatic building pressure variations, as indicated in this example.27

 

Control Scheme #3:
Space Static Pressure Control of the Return Fan (Systems with a Return or Relief Fan)

Some design engineers argue that controlling the return fan to space static pressure assures positive building pressure. Static pressure control is susceptible to the following factors, which should be seriously considered prior to the selection of this technique for control.

  • Differential pressures less than 0.05 in. WG are very difficult to control in the field.
  • The outside pressure tap can not be placed where it is unaffected by wind.
  • A single inside pressure tap can not be located to assure positive pressure throughout the building.
  • Affordable static pressure sensors can not provide the accuracy and stability required for proper control.

<Prev 1 2 3 4 5 6 7 8 9 10 11 Next>

 Home | Products | Support | Literature | Contact Us | News | Representative Locator | Catalog Registration | IAQ Resources | Giveaway Registration | Site Map
Ebtron, Inc.
1663 Hwy 701 S
Loris, SC 29569
Phone: 1.800.232.8766
©1984 - 2005 Ebtron, Inc.     Privacy Statement